電熱水鍋爐http://yangchuncity.com/房的鼓風機和引風機噪聲一般在90分貝左右,因輸送的熱水鍋爐煙氣溫度高達180度,采用封閉隔聲會導致散熱不良,電機溫度過高,甚至燒毀電機。那么電熱水鍋爐風機噪音應(yīng)該如何解決呢?
對電熱水鍋爐房的工藝布置保持小變,將鼓風機、引風機分別置在隔聲室內(nèi),用通風管將它們與主機相連接,在隔聲室頂上或墻而上開設(shè)進氣日,并安裝消聲器供機房進風使用。平而布置時將鼓風機靠近鍋爐房一側(cè),進風日在上風側(cè),電機置于氣流通道中間。鍋爐運行時,由于鼓風機在隔聲室內(nèi)產(chǎn)生負壓,大量的室外新鮮空氣就會自動進入隔聲室,首先和引風機電機進行熱交換,使之冷卻降溫,室內(nèi)溫度保持500C左右。該方案中由于隔聲室和進風消聲器的降噪能力都比較大,降噪的效果容易實現(xiàn)。鼓風機將預(yù)熱的空氣送入鍋爐燃燒,回收利用能源,具有一定的經(jīng)濟效益。
For electric water boiler room to keep small change process layout, the blower, Fan noise respectively, set in the room, with a ventilation pipe connected to their hosts, soundproof room at the top or on the wall and open the intake date, and installation muffler inlet for the engine room use. The blower near the boiler room to one side flat and arranged into the wind at the windward side of the day, the motor placed in the middle of the air flow channel. Boiler operation, due to the negative pressure in the acoustic indoor blower, lots of fresh outdoor air will automatically enter the acoustic chamber, the first and induced draft fan motor heat exchange, so that cool-down, keep the indoor temperature of about 500C. The program due acoustic chamber and inlet muffler noise reduction capabilities are large, easy to implement noise reduction effect. Blowers preheated combustion air into the boiler, recycling energy, with certain economic benefits.
為保證治理效果和電熱水鍋爐http://yangchuncity.com/設(shè)備正常運行,在設(shè)計施工中,應(yīng)根據(jù)具體要求,考慮噪聲的聲強、聲頻等因素,對隔聲、吸聲和通風散熱進行詳細設(shè)計,做好細部處理。對隔聲室的大小厚度,吸聲材料的種類、厚度進行計算。進風消聲器的消聲量一般選25dB的鋼絲網(wǎng)水泥粉刷,將玻璃纖維棉固定在鋼板上,吸收隔聲室內(nèi)的混響噪聲。
To ensure the effectiveness of governance and electric water boiler equipment uptime, during design and construction, should be based on the specific requirements, consider the noise sound intensity, audio and other factors, sound insulation, sound absorption and ventilation detailed design, good detail treatment. The thickness of the insulation chamber size, the type of sound-absorbing material, the thickness calculated. Muffler inlet muffler general election 25dB of ferro-cement stucco, glass fiber cotton fixed on the plate, absorbing acoustic noise reverberation chamber.